Product details

CONSTRUCTION:

1. Stranded copper conductor class 2

2. XLPE insulation

3. PP Filling

4. Non-woven fabrics wrapping

5. PVC inner sheath

6. Steel wire armored 

7. Non-woven fabrics wrapping

8. PVC outer sheath

APPLICATION

YJV32-Copper Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed Power&Mains Cable.

Copper XLPE SWA PVC LSZH Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 0.6/1kV.

CABLE STANDARDS

GB/T12706-2008,IEC,BS,VDE,ASTM and etc. upon request.



  

BASIC INFORMATION

Code Name 

YJV32

Rated Voltage (Uo/U)

0.6/1KV

Cable Structure

Copper Conductor / XLPE Insulation / Steel Wire Armoured / PVC Sheath

CONSTRUCTION

Conductor

Number of conductors:1,2,3,4,5,3+1,4+1

The conductors shall comply with the requirement given in IEC

Insulation

XLPE (Cross-linked Polyethylene) according to IEC

Sheath

PVC(Polyaluminium Chloride) according to IEC

Armoured

Steel Wire

CHARACTERISTICS

Conductor temperature

Maximum conductor temperature in normal use: 90℃

Max.short-circuit temperature

Maximum shall not exceed 250℃(5s Max,Duration)

Installation temperature

Ambient temperature under installation shall not be below 0℃

Minimum bending radius

The bending radius of cable: (D-Diameter of cable) 

————————————-≥15D

Description:



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Alum Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

1x4

2.3

0.7

1.0

0.8

1.8

10.9

1x6

2.8

0.7

1.0

0.8

1.8

11.4

1x10

3.6

0.7

1.0

0.8

1.8

12.2

1x16

4.5

0.7

1.0

0.8

1.8

13.1

1x25

5.6

0.9

1.0

0.8

1.8

14.6

1x35

6.7

0.9

1.0

1.25

1.8

16.6

1x50

8.0

1

1.0

1.25

1.8

18.1

1x70

9.4

1.1

1.0

1.25

1.8

19.7

1x95

11.0

1.1

1.0

1.6

1.8

22.0

1x120

12.4

1.2

1.0

1.6

1.8

23.6

1x150

13.8

1.4

1.0

1.6

1.8

25.4

1x185

15.3

1.6

1.0

1.6

1.8

27.4

1x240

17.5

1.7

1.0

1.6

1.9

29.9

1x300

19.5

1.8

1.0

2.0

2.0

33.1

1x400

22.6

2

1.2

2.0

2.2

37.3

1x500

25.2

2.2

1.2

2.0

2.3

40.5



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

2x1.5

1.4

0.7

1.0

0.8

1.8

12.8

2x2.5

1.8

0.7

1.0

0.8

1.8

13.6

2x4

2.3

0.7

1.0

0.8

1.8

14.6

2x6

2.8

0.7

1.0

1.25

1.8

16.5

2x10

3.6

0.7

1.0

1.25

1.8

18.1

2x16

4.5

0.7

1.0

1.25

1.8

19.9

2x25

5.6

0.9

1.0

1.6

1.8

23.6

2x35

6.7

0.9

1.0

1.6

1.8

25.8

2x50

8.0

1

1.0

1.6

1.9

29.0

2x70

9.4

1.1

1.0

2.0

2.0

33.2

2x95

11.0

1.1

1.2

2.0

2.1

37.1

2x120

12.4

1.2

1.2

2.0

2.3

40.5

2x150

13.8

1.4

1.2

2.5

2.4

45.4

2x185

15.3

1.6

1.4

2.5

2.6

49.9

2x240

17.5

1.7

1.4

2.5

2.7

55.1

2x300

19.5

1.8

1.6

2.5

2.9

60.2

2x400

22.6

2

1.6

2.5

3.1

67.7



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

3x1.5

1.4

0.7

1.0

0.8

1.8

13.2

3x2.5

1.8

0.7

1.0

0.8

1.8

14.1

3x4

2.3

0.7

1.0

0.8

1.8

15.2

3x6

2.8

0.7

1.0

1.25

1.8

17.1

3x10

3.6

0.7

1.0

1.25

1.8

18.9

3x16

4.5

0.7

1.0

1.25

1.8

20.8

3x25

5.6

0.9

1.0

1.6

1.8

24.7

3x35

6.7

0.9

1.0

1.6

1.8

27.2

3x50

8.0

1

1.0

1.6

1.9

30.6

3x70

9.4

1.1

1.0

2.0

2.1

35.2

3x95

11.0

1.1

1.2

2.0

2.2

39.3

3x120

12.4

1.2

1.2

2.0

2.3

43.0

3x150

13.8

1.4

1.4

2.5

2.5

48.6

3x185

15.3

1.6

1.4

2.5

2.7

53.0

3x240

17.5

1.7

1.4

2.5

2.8

58.5

3x300

19.5

1.8

1.6

2.5

3.0

64.0

3x400

22.6

2

1.6

3.15

3.3

73.5



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

(3) mm

(1) mm

(3) mm

(1) mm

mm

mm

mm

mm

3x 16/10

4.5

3.6

0.7

0.7

1

1.6

1.8

22.7

3x 25/16

5.6

4.5

0.9

0.7

1

1.6

1.8

26.5

3x 35/16

6.7

4.5

0.9

0.7

1

1.6

1.9

29

3x 50/25

8.0

5.6

1

0.9

1

1.6

2.1

33

3x 70/35

9.4

6.7

1.1

0.9

1.2

2

2.2

38

3x 95/50

11.0

8.0

1.1

1

1.2

2

2.3

42.4

3x120/70

12.4

9.4

1.2

1.1

1.2

2

2.5

48.0

3x150/70

13.8

9.4

1.4

1.1

http://www.luxingcable.com/